88 Rockwell Automation Publication 1426-UM001G-EN-P - November 2014
Chapter 5 Power Quality Monitoring
PowerQuality.V3_V1_Volts_H3_Ang (64…95, M8 model)
PowerQuality.V3_V1_Volts_H4_Ang (96…127, M8 model)
PowerQuality.I1_Amps_H1_Ang (DC…31)
PowerQuality.I1_Amps_H2_Ang (32…63)
PowerQuality.I1_Amps_H3_Ang (64…95, M8 model)
PowerQuality.I1_Amps_H4_Ang (96…127, M8 model)
PowerQuality.I2_Amps_H1_Ang (DC…31)
PowerQuality.I2_Amps_H2_Ang (32…63)
PowerQuality.I2_Amps_H3_Ang (64…95, M8 model)
PowerQuality.I2_Amps_H4_Ang (96…127, M8 model)
PowerQuality.I3_Amps_H1_Ang (DC…31)
PowerQuality.I3_Amps_H2_Ang (32…63)
PowerQuality.I3_Amps_H3_Ang (64…95, M8 model)
PowerQuality.I3_Amps_H4_Ang (96…127, M8 model)
PowerQuality.I4_Amps_H1_Ang (DC…31)
PowerQuality.I4_Amps_H2_Ang (32…63)
PowerQuality.I4_Amps_H3_Ang (64…95, M8 model)
PowerQuality.I4_Amps_H4_Ang (96…127, M8 model)
Sag and Swell Detection
The PowerMonitor 5000 unit continually monitors line voltages and sets an
alarm flag when the voltage varies below (sag) or above (swell) a predetermined
threshold, expressed as a percentage of the nominal system voltage. The
PowerMonitor 5000 models detect and report sags and swells in different ways:
The M5 model detects sags and swells and reports them in the Alarm Log.
The M6 and M8 models retain the simple sag/swell capabilities of the
M5 model but also permit you to adjust sag and swell thresholds. In
addition, fixed sag and swell thresholds corresponding to definitions found
in IEEE 1159 and EN 50160 independently detect and report sags and
swells. When sags or swells are detected, these models record waveforms
and record detailed event information in the Power Quality Log.
Setup
Basic metering configuration is required:
All models include fixed thresholds for sag and swell alarming: 90% of
nominal for sags, 110% of nominal for swells, each with a 2% of nominal
hysteresis.
In the M6 and M8 models, multi-level sag and swell thresholds and
hysteresis are user-configurable and can be adjusted by use of the
Configuration.PowerQuality web page or data table. The parameters are
listed in Ta bl e 1 4
. Defaults have been selected to effectively disable user-
configurable sag and swell detection, to avoid creating redundant events in
the Power Quality Log.